JMD points to an auxiliary command already in progress. It is not a missing-option alarm.

Contents
  1. MDI panel entry is not ordinary MDI execution
  2. With 1005#0 set, check the preceding auxiliary command
  3. Without JMD, do not assume the option is absent
  4. Verify the option without running a test move
  5. References

MDI panel entry is not ordinary MDI execution

FANUC lists A02B-0350-J667 as Manual Numerical Command for 0i-MF Plus. It allows a limited set of commands entered on the MDI panel to run in JOG mode when jog feed is ready. The catalogue lists G00, G01, G28, G30 for the second through fourth reference positions, and M/S/T/B. This is not general-purpose MDI execution; individual actions depend on the machine configuration. The minimum CNC software release was not verified.

With 1005#0 set, check the preceding auxiliary command

B-64695EN/01 labels diagnosis 1005#0 JMD under reasons why a start cannot be performed. It means that an M/S/T/B manual numeric command was specified while M/S/T/B was already executing. If the second command will not start and JMD is set, compare both commands’ timing and machine status records to see whether the earlier action is still in progress. Do not repeat the command or force a completion signal.

Without JMD, do not assume the option is absent

Check whether the control was in JOG and jog feed was ready, then verify that the requested command belongs to a supported category. If there is an alarm, record its full number and text. Diagnosis 1006#1 (ALM) on the same page simply indicates that an alarm is present; it is distinct from JMD and does not identify the cause. JMD is a diagnostic bit, not a numbered PS alarm or an entitlement test. No dedicated missing-J667 alarm was verified.

Verify the option without running a test move

Give FANUC or the machine builder the serial number, software series and revision, option record, rejected command and recorded diagnostics. Entitlement, machine readiness and an auxiliary command in progress are separate checks. Do not issue motion, force PMC signals or alter parameters to test entitlement.

References