FANUC 0i-MF Plus J704: where to start when a scale-equipped axis raises SV0421

Published Updated

SV0421 reports a disagreement between position feedback readings. Neither the scale nor the alarm establishes J704 entitlement.

Contents
  1. J704 is not the same as fitting a scale
  2. Which positions does SV0421 compare?
  3. Read-only checks after detector replacement
  4. Separate entitlement from diagnosis
  5. References

J704 is not the same as fitting a scale

FANUC lists A02B-0350-J704 as Dual Position Feedback for the 0i-MF Plus. Dual position feedback uses position feedback from both the motor side and a separate detector. The catalogue describes it as a way to improve closed-loop stability on machines with high load inertia or large backlash. A scale does not prove that this control method is active. No minimum software revision was verified.

Which positions does SV0421 compare?

The 0i-F Plus maintenance manual lists EXCESS ERROR(SEMI-FULL). SV0421 occurs when the difference between semi-closed-loop and full-closed-loop feedback exceeds the limit associated with parameter 2118. It does not identify which reading is at fault. For the applicable amplifiers, FANUC’s βi manual identifies the conversion coefficient and scale connection direction as things to check. Do not transfer a drive configuration or parameter settings from another machine.

Read-only checks after detector replacement

If the problem started after a scale change, record the alarmed axis, whether it occurred at power-up or machining, both detector models and the original backup. Have service staff compare the existing conversion configuration with the detector specification and verify feedback direction against the builder’s drawings. Do not assume the scale is defective, raise the alarm limit, disable monitoring or jog to test entitlement. For a documentation example on a different series, see the Model B read-only FSSB record guide (Chinese); do not reuse its screens or settings.

Separate entitlement from diagnosis

Give FANUC or the builder the machine serial number, CNC software series and revision, option record, detector and servo models. Ask them to confirm J704 availability and supported configuration. No dedicated missing-J704 alarm was verified. Use the approved service and acceptance procedure for the machine; changing settings does not grant entitlement.

References