FANUC 31i-B R953: why the FTP session count can exceed the PC count

Published Updated

Count FTP sessions at the CNC, not computers or application windows, and separate a connection limit from a panel difference or SR2038.

Contents
  1. R953 extends the Data Server FTP service
  2. Read the current client list
  3. A missing menu is not the same as a communication alarm
  4. Manufacturer references

Count FTP sessions at the CNC, not computers or application windows, and separate a connection limit from a panel difference or SR2038.

R953 extends the Data Server FTP service

FANUC’s 2021 function catalogue, p. 620, lists A02B-0327-R953 as Data Server Explorer Connection for the non-Plus 31i-B. It extends an existing Data Server FTP service. B-64014EN/05 documents an increase from five to ten server connections and a dedicated maintenance screen. This is not extra NC program storage or evidence that the machine can execute programs from an external device. Neither a minimum CNC software revision nor compatibility with a current PC file manager was verified. Ask FANUC or the machine builder to check eligibility and handle authorized installation using the serial number, control and software revisions, existing Data Server configuration and option record.

Read the current client list

On an applicable 31i-B, find [FTP SERVER] under [ETHER NET]. Read CLIENT LIST and record the number of rows at the time of the issue, connection durations and any repeated client addresses. The manual warns that one FTP application can use several FTP client connections internally. As an offline example, three PCs using two, two and one sessions account for five CNC connections, not three. Do not create extra sessions on a production machine to prove the limit. The manual says CLIENT DETAIL is absent on the 15-inch display unit and cannot be opened when the list is empty. Observe the list without disconnecting sessions.

A missing menu is not the same as a communication alarm

If basic FTP works but the dedicated maintenance screen is absent, check the R953 entitlement record, panel type and manual scope first. No alarm dedicated to missing R953 or fixed client wording for a full session table was verified. For SR2038 (WRONG COMMUNICATION COMBINATION), the manual points to an invalid combination of communication function and hardware option. Read diagnosis 4400 and 4401: for example, detail 2 in 4401 points to an absent hardware option identified by 4400. This is not an R953-specific indication. Share the record with the builder or network administrator rather than changing communication or security settings to test a theory.